CWCB WATER CIRCULATION HEATERS
INSTALLATION AND OPERATING INSTRUCTIONS
E-mail: [email protected] www.ccithermal.com
Date of Issue: May 2013
Ml239.Rev.5.01
Factory:
2721 Plymouth Drive, Oakville, Ontario, Canada L6H 5R5
Telephone: (905) 829-4422 Fax: (905) 829-4430
Toll Free: 1-800-410-3131
ISO 9001
POCC CA. HO02 H01561
Printed In Canada
1.0 INITIAL INSPECTION
1.1 Upon receipt from the carrier, inspect the heater for possible
damage in transit. If necessary, immediately report damage to
shipping company.
1.2 Verify that the nameplate voltage, phase, wattage and catalog
number comply with the order.
1.3 TheCWCB,whencongured:
• asaswimmingpoolheater,hasacatalognumber
CWCB-XX-1;
• asadomesticwaterordishwasherwaterboosterheater,
has a catalog number CWCB-XX-2;
• asahotwaterfurnaceforcomfortorprocesswater
heating, has a catalog number CWCB-XX-3.
These units differ in trim package, i.e. auxiliary controls. For
this reason IT IS IPORTANT THAT THE UNITS BE USED
ONLY FOR THE SPECIFIC APPICATIONS AS STATED
ABOVE.
2.0 INSTALLATION
2.1 Theheatermustbeinstalledbyqualiedpersonneltocode
requirements.
2.2 Ensure that the electrical power supply is the same voltage
andphaseastheheaterwithsufcientcurrentcapacity.
2.3 The heater must be installed in a horizontal position with the
outlet at the top and the drain at the bottom.
2.4 Themountinghardware,asprovided,issuitableforeitheroor
or ceiling mounting. Note that each mounting bracket is to be
attached at the top of the heating housing by two holding bolts
(seeFig.1).Removethetwoboltsandinstalltherstmounting
bracket prior to removing the second two bolts to install the
second mounting bracket. if all bolts are removed at once the
tank may shift which will increase installation time.
2.5 Please refer to Figure 1 for dimensions. Be sure to provide
adequate space to facilitate installation and maintenance.
Leave a minimum of 24" (60cm) clearance at the control
compartment (opposite side to the inlet). If the unit is to be
mounted under a table or cabinet a minimum of 30" (75cm)
fromtheoortotheundersideofthecabinetisrequiredfor
piping.
2.6 Allow space at sides for the conduit used for power supply and
for thermostat or optional equipment wiring.
2.7 Please refer to Figure 2 for component location and note the
following:
2.7.1 The circulation pump outlet is connected to the heater
inlet located at the end of the unit opposite to the controls
compartment.
2.7.2 Aowswitch(optional)istoensurethattheheaterwillnotbe
energizediftheowisinterrupted.Installationsrequiringaow
switch include:
(a) Swimming pool heating systems where the heater is
positioned above the pool water surface.
(b) Whenever the plumbing allows for the heater to be isolated
by shut off valves on the inlet and outlet.
(c) Systems where the heater vessel is allowed to drain when
owisinterrupted.(Withoutwaterthebuilt-inlimitwillnot
perform as intended).
(d) Systems where the temperature control bulb is located
away from the outlet.
Ifaowswitchisnotused,andalsoforpoolheating,itisbest
to allow the circulating pump to run continuously.
2.7.3 Wirebothowswitchandcontrolthermostattocontacts
designated “normally open” and “common”. “Normally open”
contacts open on temperature rise on thermostat and close on
owthroughswitch.
Seitenansicht 0
1 2 3 4 5

Inhaltsverzeichnis

Seite 1 - Page 1 of 3

MI239 REV. 4Page 1 of 3ISO 9001:2000CWCB WATER CIRCULATION HEATERSINSTALLATION AND OPERATING INSTRUCTIONSE-mail: [email protected] www.ccithermal

Seite 2

2.7.4 A pressure relief valve is a safety feature which is intended to open when the system malfunctions or is improperly operated or maintained. Uni

Seite 3 - Oakville: 1-800-410-3131

PLEASE ADHERE TO INSTRUCTIONS PUBLISHED IN THIS MANUAL.Failure to do so may be dangerous and may void certain provisions of your warranty. For further